Hydrant Count and Spacing: California Fire Code Appendix C
"Hydrant Count and Spacing: California Fire Code Appendix C" is lesson 3 of 6 in the Fire Protection (C-16) Learning Hub. It opens with "When Hydrants Are Required" and works through 5 short steps, then a worked example you can check yourself against.
One-time purchase, no subscription. Law & Business included.
Steps in this lesson
When Hydrants Are Required
Read Table C102.1 by Fire Flow
Adjust With the Table Footnotes
Which Hydrants Count
Standpipe Buildings, Clear Space and the Water Supply Test
The worked example in the course applies this lesson to a realistic job in 5 steps, from "Unsprinklered case" through "Check the standpipe rule".
What you'll be able to do
Explain the main idea of "Hydrant Count and Spacing: California Fire Code Appendix C" in plain language you can use on the exam.
Apply this step with confidence: "Adjust With the Table Footnotes".
Apply this step with confidence: "Which Hydrants Count".
Apply this step with confidence: "Standpipe Buildings, Clear Space and the Water Supply Test".
Test yourself on the worked example and the quick-check quiz inside the classroom.
The diagram for this lesson, exactly as it appears in the Learning Hub.
The first steps of this lesson
Step 1: When Hydrants Are Required
CFC Section 507.5 says fire hydrant systems must comply with Sections 507.5.1 through 507.5.6 and Appendix C, or an approved method. Under 507.5.1, where any portion of a new building is more than 400 ft from a hydrant on a fire apparatus access road, measured by an approved route around the exterior of the building, on-site hydrants and mains are provided where the fire code official requires them. For Group R-3 and Group U occupancies equipped throughout with a sprinkler system under 903.3.1.1, 903.3.1.2 or 903.3.1.3, that distance is 600 ft. Appendix C itself is not mandatory unless the jurisdiction adopts it.
Step 2: Read Table C102.1 by Fire Flow
Take the required fire flow from the Appendix B lesson and find its row in Table C102.1. Each row gives the minimum number of hydrants, the average spacing between hydrants in feet, and the maximum distance from any point on the street or road frontage to a hydrant. For example, 1,750 gpm or less needs 1 hydrant at 500 ft average spacing and 250 ft maximum distance. 3,251 to 4,000 gpm needs 4 hydrants at 350 ft and 210 ft. 5,501 to 6,000 gpm needs 6 hydrants at 250 ft and 150 ft. 7,001 gpm or more needs 8 or more hydrants at 200 ft and 120 ft.
The remaining 3 steps, the worked example and the quiz are in the course. This is a preview. The full lesson, with the step-by-step explanations, a worked example and a quick-check quiz, is inside the classroom.