The first steps of this lesson
Step 1: Luminaires must meet JA8
2025 California Energy Code §150.0(k)1A: all installed luminaires and light sources shall comply with Reference Joint Appendix JA8 and be certified and marked as required by JA8. Exceptions include integrated device lighting (exhaust fans, kitchen range hoods, bath vanity mirrors, garage door openers, ceiling fan kits subject to DOE standards); navigation lighting rated less than 5 watts such as night lights, step lights and path lights; lighting of 45 lumens per watt or more inside drawers, cabinetry or linen closets; and certain outdoor LED, decorative colored SSL, HID and induction sources. Lamps in enclosed or recessed luminaires must meet the JA8 elevated-temperature marking requirements (§150.0(k)1D).
Step 2: Recessed ceiling downlights
§150.0(k)1C: luminaires recessed into ceilings may not contain screw-base lamp sockets; must carry a label certifying the luminaire is airtight with air leakage less than 2.0 cfm at 75 Pascals when tested to ASTM E283; must be sealed with a gasket or caulk between housing and ceiling with all air leak paths between conditioned and unconditioned spaces sealed (or be installed per manufacturer's instructions to maintain airtightness); and must meet the clearance and installation requirements of California Electrical Code 410.116. An exception covers recessed luminaires marked for fire-rated installations extruded into the ceiling space and those in noninsulated ceilings. Exhaust fan housings with integral light need not be certified airtight.
The remaining 3 steps, the worked example and the quiz are in the course. This is a preview. The full lesson, with the step-by-step explanations, a worked example and a quick-check quiz, is inside the classroom.
Independent exam preparation. Contractors Classroom is not affiliated with the Contractors State License Board, and no course can guarantee a passing result.