The first steps of this lesson
Step 1: When temporary wiring is allowed
8 CCR §2405.1 permits temporary power and lighting of 600 volts or less during construction, remodeling, maintenance, repairs or demolition; for not more than 90 days at non-permanent locations such as carnivals, music festivals, Christmas decorative lighting and Christmas tree lots; and for experimental work and emergencies. It must be removed immediately when the project or purpose ends, and temporary installations over 600 volts follow the High-Voltage Electrical Safety Orders. The 2025 California Fire Code §603.8 likewise limits temporary wiring to 90 days, with an exception for periods of construction, remodeling, repair or demolition.
Step 2: Feeders and branch circuits
Per §2405.2, feeders originate in an approved distribution center and are run as multi-conductor cord or cable assemblies; branch circuits originate in an approved power outlet or panelboard. Open conductors must be fastened at ceiling height every 10 feet, and no branch-circuit conductor may be laid on the floor. Receptacles are the grounding type, each branch circuit carries a separate equipment grounding conductor unless it is in continuous grounded metallic raceway or metallic-covered cable, no bare conductors or earth returns are allowed, and switches or plug connectors must disconnect all ungrounded conductors of each temporary circuit. Multi-conductor cords must be hard service type, and cords must be protected at doorways and pinch points.
The remaining 3 steps, the worked example and the quiz are in the course. This is a preview. The full lesson, with the step-by-step explanations, a worked example and a quick-check quiz, is inside the classroom.
Independent exam preparation. Contractors Classroom is not affiliated with the Contractors State License Board, and no course can guarantee a passing result.