The first steps of this lesson
Step 1: Know Which Circuit Family You Are Pulling
Title 8 sorts low-voltage wiring into families: electric light and power; Class 1; nonpower-limited fire alarm (NPLFA); Class 2 and Class 3 remote control, signaling and power-limited circuits; power-limited fire alarm (PLFA); and communications. Every separation rule is a pair of families. 8 CCR §2586.1 says fire alarm circuits are classified as either nonpower limited or power limited, and §2586.4 requires fire alarm circuits to be identified at terminal and junction locations and PLFA circuits to be durably marked as such where plainly visible at terminations.
Step 2: Class 2 and Class 3: Barrier or Separate Enclosures
8 CCR §2585.3: for installations built on or after May 5, 2008, Class 2 and Class 3 conductors may not be placed in any cable, cable tray, compartment, enclosure, manhole, outlet box, device box, raceway or similar fitting with conductors of electric light, power, Class 1, nonpower-limited fire alarm circuits, or medium power network-powered broadband communications cables, unless a barrier or other equivalent form of protection against contact is used.
The remaining 3 steps, the worked example and the quiz are in the course. This is a preview. The full lesson, with the step-by-step explanations, a worked example and a quick-check quiz, is inside the classroom.