Step 1: Where the California Fire Code Stops and NFPA 72 Starts
2025 CFC §907 prints some design numbers itself and sends the rest to NFPA 72. Wiring, power supplies, monitoring, acceptance testing and maintenance are handed to NFPA 72 in §907.6.1, §907.6.2, §907.6.6, §907.7 and §907.8, and NFPA 72 is not a California code book on disk. So battery sizing and detector spacing are not taught here. This lesson uses the numbers CFC §907 prints. §907.6.1 also says wiring must comply with the California Electrical Code.
Step 2: Manual Fire Alarm Boxes
CFC §907.4.2.1: manual fire alarm boxes are located not more than 5 feet (1524 mm) from the entrance to each exit. In buildings not protected by an automatic sprinkler system (903.3.1.1 or 903.3.1.2), additional boxes are located so that travel to the nearest box does not exceed 200 feet (60 960 mm). §907.4.2.2: mounted not less than 42 inches (1067 mm) and not more than 48 inches (1372 mm) from the floor to the highest point of the activating handle. §907.4.2.3: red. §907.4.2.7: operable with one hand.