Step 1: Where the Rule Lives
Section 120.6(f) of the 2025 California Energy Code lists mandatory requirements for elevators. It applies to the lighting and ventilation the elevator installer connects inside the cab, so the contractor has to check the fixture and fan data before the cab is finished.
Step 2: Lighting Power Limit
The light power density for the luminaires inside the elevator cab can be no greater than 0.6 watts per square foot (120.6(f)1). Interior signal lighting and interior display lighting are not counted in the calculation (Exception to 120.6(f)1). The code prints the limit as watts per square foot without defining the area, and cab floor area is the usual basis.
Step 3: Ventilation Fan Limit
Elevator cab ventilation fans for cabs without space conditioning can not exceed 0.33 watts per cfm, measured at maximum speed (120.6(f)2). Divide the fan input watts by its maximum-speed airflow in cfm to check it.
Step 4: Automatic Shut-Off
When the cab is stopped and unoccupied with doors closed for over 15 minutes, the cab lighting and ventilation fans must be switched off until the cab runs again (120.6(f)3). Lighting and ventilation must remain operational if the cab gets stuck with passengers inside (120.6(f)4).