The first steps of this lesson
Step 1: Why a Hoistway Needs a Vent
An elevator hoistway is a tall, enclosed shaft, so in a fire it acts like a chimney for smoke and hot gases. The 2025 California Building Code (CBC) 3003.4 requires hoistways that contain the driving machine to have a means of venting smoke and hot gases to the outer air in case of fire.
Step 2: Where the Vent Goes
CBC 3003.4.1 locates the vents at the top of the hoistway. They must open either directly to the outer air or through noncombustible ducts to the outer air. A vent that discharges into the attic or a machine room does not satisfy this section.
Step 3: The Two Area Tests
CBC 3003.4.2 sets the vent area at not less than 3 1/2 percent of the area of the hoistway, and not less than 3 square feet for each elevator car. You run both tests and use the larger answer. Small single-car hoistways are usually governed by the 3 square feet per car, and wide multi-car hoistways by the percentage.
The remaining 2 steps, the worked example and the quiz are in the course. This is a preview. The full lesson, with the step-by-step explanations, a worked example and a quick-check quiz, is inside the classroom.