The first steps of this lesson
Step 1: Tight Homes Need Mechanical Ventilation
New California homes are built tight, so fresh air does not leak in on its own. California Energy Code Section 150.0(o) requires every dwelling unit to have whole-dwelling mechanical ventilation, and Section 150.0(o)1C(i) prints the equation for the total required rate. Window operation is not a permissible way to provide it (150.0(o)1A). HVAC contractors install or size the ventilation fan, or the outside-air duct on the central system, so this calculation is part of the job.
Step 2: The Equation
The total required airflow is Qtot = 0.03 x Afloor + 7.5 x (Nbr + 1), in CFM (Section 150.0(o)1C(i), Equation 150.0-B). Afloor is the dwelling-unit floor area in square feet. Nbr is the number of bedrooms and is not to be less than 1, so a studio is counted as one bedroom.