Step 1: When a Machinery Room Is Required
2025 CMC Section 1106.1 requires a refrigeration machinery room when any one of these exists: the quantity in a single independent circuit exceeds the amounts of Table 1102.3 (Section 1106.1.1); direct- or indirect-fired absorption equipment is used (1106.1.2); an A1 system has an aggregate combined compressor horsepower of 100 or more (1106.1.3); or the system contains other than a Group A1 refrigerant (1106.1.4). Equipment located outdoors is allowed under ASHRAE 15 as the Exception to Section 1106.1 says, so a rooftop or yard rack is a different path.
Step 2: Emergency Exhaust: Q = 100 x the Square Root of G
Section 1106.2.9 requires an emergency ventilation system able to exhaust a leak or rupture. For A1, A2, A3, B1, B2 and B3 refrigerants, Equation 1106.2.9.1 gives Q = 100 x the square root of G, where Q is airflow in cfm and G is the pounds of refrigerant in the largest system. Where several refrigerants are present, the highest airflow quantity applies. Group A2L and B2L rooms use the separate method in Section 1106.11.11.