Step 1: A Closed Hot-Water System Must Have an Expansion Tank
Heated water takes up more room, and in a closed loop the extra volume has nowhere to go. 2025 CMC §1004.1 requires an expansion tank in a hot-water-heating system to control the pressure increase from thermal expansion, and §1209.1 requires one in each closed hydronic system, of the closed type and rated for the pressure of the system. The tank must be supported to carry twice the weight of the tank filled with water without straining the connecting piping (§1004.1, §1209.2), and it must be piped so it can be drained without emptying the system.
Step 2: Open Versus Closed Tanks
An open-type tank must sit at least 3 feet above the highest point of the system, with an overflow at the top of at least half the size of the supply pipe or at least 1 inch, discharging through an air gap into the drainage system (§1004.2). A closed-type system needs an airtight tank or other approved air cushion, designed for a hydrostatic test pressure of 2-1/2 times the allowable working pressure; a tank for a system operating above 30 psi must comply with ASME BPVC Section VIII.1 (§1004.3, §1209.3). The shutoff to the tank must stay open in operation, with the valve handle locked open or removed (§1209.2), and non-diaphragm tanks get isolation valves at their connections (§1212.7).