Hydronic and Steam Pipe Insulation (Energy Code Table 120.3-A-1)

"Hydronic and Steam Pipe Insulation (Energy Code Table 120.3-A-1)" is lesson 5 of 7 in the Boiler and Steam Fitting (C-4) Learning Hub. It opens with "What the Energy Code Makes You Insulate" and works through 5 short steps, then a worked example you can check yourself against.

One-time purchase, no subscription. Law & Business included.

Steps in this lesson

  1. What the Energy Code Makes You Insulate
  2. Read Table 120.3-A-1 by Temperature Row and Pipe Size Column
  3. Insulation That Is Not in the Conductivity Range
  4. Protect the Insulation
  5. Related Limits: Supply Temperature and Touch Surfaces

The worked example in the course applies this lesson to a realistic job in 4 steps.

What you'll be able to do

  • Explain the main idea of "Hydronic and Steam Pipe Insulation (Energy Code Table 120.3-A-1)" in plain language you can use on the exam.
  • Apply this step with confidence: "Insulation That Is Not in the Conductivity Range".
  • Apply this step with confidence: "Protect the Insulation".
  • Apply this step with confidence: "Related Limits: Supply Temperature and Touch Surfaces".
  • Test yourself on the worked example and the quick-check quiz inside the classroom.
Pipe Insulation Thickness (Table 120.3-A-1)INSULATED PIPE (SECTION)PIPEthicknesst = 2.0 in2 in condensate return, 200 Ftable thickness 2.0 inTABLE 120.3-A-1 (excerpt, inches)Fluid temprange FConductivityBtu-in/h-sq ft-FNominal pipe diameter, inches<11-1.51.5-44-88+Above 350.32-.344.55.05.05.05.0251-350.29-.323.04.04.54.54.5201-250.27-.302.52.52.53.03.0141-200.25-.291.51.52.02.02.0105-140.22-.281.01.51.51.51.5Highlighted: the three lines in the worked exampleWORKED EXAMPLE ANSWERS6 in steam main, 240 F: row 201-250, 4 to under 8 in column = 3.0 in2 in condensate return, 200 F: row 141-200, 1.5 to under 4 in column = 2.0 in3/4 in hot-water branch, 180 F: row 141-200, under 1 in column = 1.5 inAlternate K = 0.31 (outside .25-.29): T = PR[(1 + t/PR)^(K/k) - 1] = 1.1875 x (3.403 - 1) = 2.85 inInsulate to 3.0 in, 2.0 in and 1.5 in; higher-conductivity foam needs 2.85 inSource: 2025 California Energy Code 120.3(a), 120.3(b), 120.3(c), Table 120.3-A-1; CMC 1201.2CC
The diagram for this lesson, exactly as it appears in the Learning Hub.

The first steps of this lesson

Step 1: What the Energy Code Makes You Insulate

2025 Energy Code §120.3 applies to nonresidential and hotel/motel buildings. Under §120.3(a)2, space-heating piping (steam, steam condensate and hot water fluid distribution systems) must be insulated, and the fluid distribution system includes the elements in series with the flow: pipes, fittings, pumps, valves, strainers, coil u-bends and air separators, but not expansion tanks, fill lines, chemical feeders and drains. Exceptions include factory-installed piping within certified equipment, piping with a design operating temperature between 60 F and 105 F, framing penetrations, and fluid pumps, steam traps and blow-off valves (Exceptions 1 to 6).

Step 2: Read Table 120.3-A-1 by Temperature Row and Pipe Size Column

Find the fluid operating temperature range, then the nominal pipe diameter column. Minimum thickness in inches (columns: under 1 in / 1 to under 1.5 / 1.5 to under 4 / 4 to under 8 / 8 and larger): above 350 F: 4.5 / 5.0 / 5.0 / 5.0 / 5.0; 251-350 F: 3.0 / 4.0 / 4.5 / 4.5 / 4.5; 201-250 F: 2.5 / 2.5 / 2.5 / 3.0 / 3.0; 141-200 F: 1.5 / 1.5 / 2.0 / 2.0 / 2.0; 105-140 F: 1.0 / 1.5 / 1.5 / 1.5 / 1.5. The thicknesses assume insulation conductivity in the range printed for that row (for example 0.25 to 0.29 Btu-in/h-sq ft-F for 141-200 F, at a 125 F mean rating temperature).

The remaining 3 steps, the worked example and the quiz are in the course. This is a preview. The full lesson, with the step-by-step explanations, a worked example and a quick-check quiz, is inside the classroom.