The first steps of this lesson
Step 1: Spacing Is a Code Number, Not a Habit
Screws are what actually hold board to framing, so the maximum spacing is printed in the code, not left to the hanger's judgment. For houses and townhouses the printed table is 2025 CRC Table R702.3.5. For other occupancies, 2025 CBC Section 2508.1 and Table 2508.1 send you to GA-216 and ASTM C840, and the CBC itself prints fastener spacing only for specific assemblies (Table 721.1(2)) and diaphragm ceilings (Table 2508.6). Too few screws is how you get sagging ceilings and popped fasteners.
Step 2: The Maximum-Spacing Table
2025 CRC Table R702.3.5 lists the maximum spacing of fasteners. For 1/2 in. board without adhesive: a wall on 16 in. o.c. studs allows screws at 16 in.; a wall on 24 in. o.c. studs needs 12 in.; a ceiling needs 12 in. whether the board runs either direction on 16 in. framing or perpendicular on 24 in. framing. 5/8 in. board follows the same pattern: 16 in. on 16 in. o.c. walls, 12 in. on 24 in. o.c. walls and on ceilings. The only time screws reach 16 in. is a wall on 16 in. framing.