Masonry (C-29) · Lesson 3 of 8Chimney Height, Cricket, Spark Arrester and Clearances
"Chimney Height, Cricket, Spark Arrester and Clearances" is lesson 3 of 8 in the Masonry (C-29) Learning Hub. It opens with "The 3-2-10 Termination Rule" and works through 5 short steps, then a worked example you can check yourself against.
One-time purchase, no subscription. Law & Business included.
The first steps of this lesson
Step 1: The 3-2-10 Termination Rule
2025 CRC R1003.9 (CBC 2113.9) sets two tests for how high a masonry chimney goes, and the chimney must pass both. It extends at least 3 feet above the highest point where the chimney passes through the roof, and at least 2 feet higher than any portion of the building within 10 feet. Work out the top elevation each rule gives and build to the higher one. The 10-foot distance is measured horizontally from the chimney to the nearest part of the building, usually the ridge or a taller roof wall.
Step 2: Chimney Cap and Cricket
A masonry chimney gets a concrete, metal or stone cap sloped to shed water, a drip edge, and a caulked bond break around any flue liner (R1003.9.1). Where the chimney dimension parallel to the ridgeline is greater than 30 inches and the chimney does not intersect the ridgeline, a cricket is required, flashed and counterflashed like a normal roof-chimney joint (R1003.20). Table R1003.20 gives the cricket height H as a fraction of the chimney width W by roof slope: 12:12 is W/2, 8:12 is W/3, 6:12 is W/4, 4:12 is W/6, 3:12 is W/8.
The remaining 3 steps, the worked example and the quiz are in the course. This is a preview. The full lesson, with the step-by-step explanations, a worked example and a quick-check quiz, is inside the classroom.