The first steps of this lesson
Step 1: The Grout Itself and the Time Limit
2025 CRC R606.2.12 allows grout made to ASTM C476 or to the proportions in Table R606.2.12 (by volume: 1 part portland or blended cement, 0 to 1/10 hydrated lime, and damp loose aggregate of 2 1/4 to 3 times the cementitious volume for fine grout; coarse grout adds 1 to 2 times the cementitious volume of coarse aggregate). Type M or S mortar with enough water added for pouring consistency may also be used as grout. Under R606.3.5.1 grout is a plastic mix that pumps without segregation, is placed before initial set and not more than 1 1/2 hours after water is added, is consolidated by puddling or mechanical vibration, and is reconsolidated after the excess water is absorbed but before it loses plasticity. Never pump it through aluminum pipe.
Step 2: Lift Height and Pour Height
Grout is poured in lifts of 8 feet maximum. Where the total grout pour exceeds 8 feet, the lifts are limited to 64 inches and special inspection during grouting is required (R606.3.5.1; CBC 2101.3 sends masonry special inspection to Chapter 17). If work stops for 1 hour or longer, stop all tiers at the same elevation with the grout 1 inch below the top to form the horizontal construction joint. Table R606.3.5.1 ties pour height to the space available: fine grout needs a 0.75 in space (1.5 x 2 in cell) for a 1-ft pour, 2 in (2 x 3) for 5 ft, 2.5 in (2.5 x 3) for 12 ft and 3 in (3 x 3) for 24 ft; coarse grout needs 1.5 in (1.5 x 3), 2 in (2.5 x 3), 2.5 in (3 x 3) and 3 in (3 x 4) for the same heights.
The remaining 3 steps, the worked example and the quiz are in the course. This is a preview. The full lesson, with the step-by-step explanations, a worked example and a quick-check quiz, is inside the classroom.
Independent exam preparation. Contractors Classroom is not affiliated with the Contractors State License Board, and no course can guarantee a passing result.