Step 1: Why Rapid Shutdown Labels Exist
A PV array keeps producing voltage whenever light hits it, even when the building's power is off, so firefighters have to know which parts of the system the rapid shutdown switch actually de-energizes. 2025 California Fire Code Section 1205.4 says buildings with rapid shutdown PV systems shall have permanent labels in accordance with Sections 1205.4.1 through 1205.4.3. CFC Section 1205.1 says the electrical portion of the PV system is installed under the California Electrical Code, so the label rules here sit on top of the wiring rules.
Step 2: Two Label Types, Chosen by What Shuts Down
CFC Section 1205.4.1 Item 1 is for systems that shut down the array AND the conductors leaving the array: the first two lines are uppercase, at least 3/8 inch (10 mm) tall, black on a yellow background, and the remaining characters are uppercase, at least 3/16 inch (5 mm) tall, black on white, per Figure 1205.4.1(1). Item 2 is for systems that only shut down the conductors leaving the array: the first two lines are uppercase, at least 3/8 inch (10 mm) tall, white on a red background, and the rest are at least 3/16 inch (5 mm) tall, black on white, per Figure 1205.4.1(2). Item 2's wording ends with the warning that conductors within the array remain energized in sunlight.