The first steps of this lesson
Step 1: The Rule: Every New Single-Family Home Gets PV
2025 California Energy Code Section 150.1(c)14 says all single-family residential buildings shall have a newly installed photovoltaic (PV) system (or newly installed PV modules) meeting the qualification requirements of Joint Appendix JA11. The annual electrical output must be no less than the smaller of two numbers: the size from Equation 150.1-C, or the building's solar access roof area (SARA) times 18 for steep-sloped roofs (times 14 for low-sloped roofs). This is the first number a solar contractor sizes a new-home system to.
Step 2: Equation 150.1-C: Two Terms, Two Table Factors
Section 150.1(c)14 prints the equation as kWpv = (CFA x A)/1000 + (Ndu x B), and the result is the kWdc size of the PV system. CFA is the conditioned floor area in square feet, Ndu is the number of dwelling units, and A and B come from Table 150.1-C by climate zone. For example, Table 150.1-C lists Climate Zone 12 as A = 0.613 and B = 1.40, and Climate Zone 3 as A = 0.628 and B = 1.12. Divide the CFA term by 1000 so it comes out in kW.